| The performance data in this website
was acquired by elaborate test work so that heating and cooling system
designers would have accurate data for registers and diffusers.
GENERAL SELECTION PROCEDURE
1. When the heat loss or heat gain in Btuh for each room is not
specified, it should be calculated in accordance with the methods
outlined in the current ASHRAE Guide.
2. Determine the number of outlets needed per room. At least one
supply for each exposed wall in each room should be used for heating,
except that only one supply may be used in bedrooms which have less
than 7,000 Btuh heat loss and are located over a heated space. Select
at least one heat outlet for each 8,000 Btuh heat loss or 4,000
Btuh heat gain for a room, whichever is greater. The use of several
small supplies, each handling moderate air volumes, in place of
using fewer and larger supplies may be necessary for better air
distribution, and will cut down dirt streaking.
3. The Btuh delivery required for each room supply is determined
by dividing the total room heat loss or gain by the number of outlets.
4. Refer to the Heat Conversion Chart on page 18 to find the CFM
that will deliver the required Btuh at the desired supply air temperature.
5. Select from the performance data the type and size of diffuser
that gives the desired air pattern (spread and throw), at the CFM.
It is usually standard practice to use the cooling conversion chart
for year round air conditioning, unless the heating requirements
are larger, as the larger CFM required for cooling can be dampered
down (lower than fan speed, etc.) for heating. Make sure the pressure
loss is within your blower capacity.
All tests used in compilation of performance data in this website were conducted under isothermal conditions (supply air and room air termperatures being equal), therefore, the throw data will be slightly greater for heating and slightly less for cooling.
|